How to use this furnace size calculator
- Pick your city. It sets the climate zone, the winter design temperature and the heating degree days for 71 US cities. If yours isn't listed, pick the nearest one or enter your own numbers.
- Choose a method. "By square footage" is the quick rule of thumb. "From my fuel bills" takes last year's gas, propane or oil use and works out what your house actually loses. Use the bills if you have them.
- Describe the new furnace. Gas or propane at the efficiency (AFUE) you are pricing, or electric at your supply voltage.
- Add your current furnace if you like. The input and output figures are on the rating plate. The tool tells you how it compares with the load.
- Read the ladder. Every standard size is shown against your load. The one marked "Pick" is the smallest that covers it. Anything in the shaded band is within the Manual S limit.
Why this furnace calculator is different
Most furnace size calculators multiply your square footage by a number for your climate and stop there. The number varies from site to site, nobody says where it came from, and it runs high. This one does more.
- It can measure your house. Your fuel bills record how much heat the house lost last winter. The tool turns that into a design load, the method state efficiency programs use to size replacement heating. None of the calculators we checked on Google's first page do it.
- It checks the limit on oversizing. A furnace's output should be 100% to 140% of the design load. The tool shows where every standard size lands, so you can see when a quote is two sizes too big.
- It keeps input and output apart. Furnaces are sold by input. Your house needs output. An 80,000 Btu/h furnace delivers 64,000 at 80% AFUE and 76,800 at 96%, and the tool does that conversion for every size.
- It checks the furnace you already have. Many replacements are like for like. If the old one was oversized, that copies the mistake.
- It uses real local climate data, not a five-region map: ASHRAE design temperatures and NOAA degree days, matched to the same airport weather station.
How it works (the math)
Square-footage method. The rule of thumb behind most furnace calculators, using the same table as our BTU calculator so the two tools agree:
Load (Btu/h) = sq ft x zone factor x (ceiling ft / 8) x insulation
zone factor = 30, 35, 40, 45, 50, 55, 60 Btu/h per sq ft for zones 1 to 7
insulation = 1.2 poor, 1.0 average, 0.9 good Fuel-bill method. Last year's heating fuel, times the old furnace's efficiency, is the heat the house lost. Divide by the year's heating degree-hours and you have the house's heat loss per degree. Multiply by how far the design day falls below 65°F:
Heating fuel = 12-month use - 12 x summer-month use
Heat delivered = heating fuel x Btu per unit x old AFUE
UA (Btu/h per F) = heat delivered / (HDD65 x 24)
Design load = UA x (65 - 99% design temperature)
Btu per unit (EIA): therm 100,000 | CCF 103,600 | propane gal 91,452 | heating oil gal 138,500 The 65°F base matches the degree days. Efficiency Maine's Heat Load Estimator uses the same pairing, and GreenBuildingAdvisor's version of the method applies the equipment efficiency as this tool does. The summer subtraction, which takes out the water heater, stove and dryer, follows the Massachusetts Clean Energy Center's gas-bill worksheet.
Matching it to a furnace. Output = input x AFUE. A size fits when its output is 100% to 140% of the design load:
Input that fits = load / AFUE to 1.4 x load / AFUE
Electric (Btu/h) = kW x 3,412 (x 0.75 on a 208 V supply) The 140% ceiling is ACCA Manual S. ENERGY STAR writes it into its HVAC design rules as 100% to 140% of the design heat loss for a heating-only furnace, and allows more when the furnace blower also has to move air for central AC. Gas sizes are the 40,000 to 140,000 Btu/h input steps manufacturers sell. Electric sizes are heat kit ratings at 240 V from Goodman's spec sheet, with its 0.75 factor for 208 V.
Worked examples
A 2,000 square foot house in Chicago, by square footage
Chicago is zone 5, so the rule gives 2,000 x 50 = 100,000 Btu/h. At 96% AFUE the smallest furnace that covers it is a 120,000 Btu/h input, putting out 115% of the load. At 80% it takes a 140,000. That is what most calculators, and many quotes, would tell you.
The same house, by its gas bill
The owner burned 1,000 therms last year, about 20 a month in summer. Take out twelve summer months and 760 therms went to heat. Through an 80% furnace that is 60.8 million Btu delivered. O'Hare averages 5,974 heating degree days, so the house loses about 424 Btu/h per degree. Chicago's design temperature is 3.3°F, which is 61.7 degrees below 65, so the design load is 26,200 Btu/h.
The rule of thumb was 3.8 times that. Even a 40,000 Btu/h furnace, the smallest standard size, puts out 147% of this load, so the tool points to a two-stage or modulating model. The 100,000 Btu/h furnace in the basement is 305% of the load. It runs in short bursts all winter.
That gap is the normal result. A 2026 study by researchers at Purdue and Trane, funded in part by the Department of Energy and not yet peer reviewed, measured 74 houses in five climate zones. Their existing furnaces averaged 2.96 times the bill-method load, and a square-footage rule like this one gave the highest estimate of any method tested.
An electric furnace in Atlanta
A 1,500 square foot house in zone 3 comes to 60,000 Btu/h by the rule of thumb. At 240 V a 20 kW heat kit covers it (109% of the load). On a 208 V supply, common in apartments, the same kit makes only three quarters of its rated heat, so it takes a 25 kW kit (102%). If you are sizing electric heat this big, price a heat pump too.
What the estimate can't see
- The bill method reads low if you heated with a wood stove or space heaters, kept the house cold, or left it empty for part of the winter. It reads high if the year was colder than normal. Use a typical year.
- It needs one fuel doing the heating. It does not work for homes heated with electricity, because the summer baseline includes air conditioning.
- Leaky ducts in an attic or crawlspace lose heat the bills already include, but a rule of thumb does not know about them.
- Neither method is a Manual J. For a replacement, ask the contractor for the Manual J load and the quoted furnace's output, and check both against this.
- Efficiency standards are changing. Federal rules require new non-weatherized gas furnaces to reach 95% AFUE from December 18, 2028. The rule is under legal challenge, so check its status before you buy an 80% unit.
Frequently asked questions
What size furnace do I need for a 2,000 square foot house?
By the usual rule of thumb, 60,000 Btu/h of output in a warm climate up to 120,000 in a very cold one. In Chicago that is 100,000 Btu/h, a 120,000 input furnace at 96% AFUE. Measured from fuel use, most houses need far less: the Chicago example above came to 26,200 Btu/h. Run your own bills through the tool before you accept a size.
How many BTU per square foot does a furnace need?
Rules of thumb use 30 Btu/h per square foot in the warmest US climates and 60 in the coldest. Worked out from fuel use, the Chicago house above needs 13.1. The tool shows the figure for your house in the "Per square foot" box.
What is the difference between furnace input and output BTU?
Input is the gas the furnace burns per hour, and it is the number in the model name. Output is the heat that reaches the ducts: input times efficiency. A 100,000 Btu/h furnace at 80% AFUE puts out 80,000. Size the output to the load, then pick the input that gets you there.
Is it bad to oversize a furnace?
Yes. An oversized furnace heats the house in short bursts and shuts off, so rooms swing in temperature, the blower is loud, and the igniter and controls wear faster. Carrier warns that excessive oversizing can make the furnace or its vent fail early. Manual S caps the output at 140% of the load.
Can I size a furnace from my gas bill?
Yes, and it is one of the better checks a homeowner can do. You need a year of use, a typical summer month to subtract the water heater and stove, the old furnace's efficiency, and your area's degree days and design temperature. The tool has the climate data built in for 71 cities.
Design temperatures and degree days by city
The climate data inside the tool, for reference. The design temperature is the ASHRAE 2021 99% heating dry-bulb: the outdoor temperature the airport stays above for 99% of the hours in the year. Degree days are NOAA's 1991 to 2020 normals at base 65°F, from the same station.
Show all 71 cities
| City | Zone | 99% design | HDD65 |
|---|---|---|---|
| Anchorage, AK | 7 | -2.8°F | 9,979 |
| Fairbanks, AK | 8 | -37.6°F | 13,420 |
| Birmingham, AL | 3A | 24.9°F | 2,533 |
| Little Rock, AR | 3A | 24°F | 3,165 |
| Flagstaff, AZ | 5B | 9.9°F | 6,746 |
| Phoenix, AZ | 2B | 41.9°F | 874 |
| Fresno, CA | 3B | 34.8°F | 2,187 |
| Los Angeles, CA | 3B | 47°F | 1,214 |
| Sacramento, CA | 3B | 33.6°F | 2,644 |
| San Diego, CA | 3B | 47.2°F | 990 |
| San Francisco, CA | 3C | 42.2°F | 2,475 |
| Denver, CO | 5B | 5.8°F | 5,862 |
| Hartford, CT | 5A | 9.1°F | 5,883 |
| Washington, DC | 4A | 20.7°F | 3,769 |
| Wilmington, DE | 4A | 16.9°F | 4,647 |
| Jacksonville, FL | 2A | 32.8°F | 1,228 |
| Miami, FL | 1A | 52.7°F | 104 |
| Atlanta, GA | 3A | 26.4°F | 2,531 |
| Honolulu, HI | 1A | 65.1°F | 0 |
| Des Moines, IA | 5A | 0.4°F | 6,178 |
| Boise, ID | 5B | 16.4°F | 5,321 |
| Chicago, IL | 5A | 3.3°F | 5,974 |
| Indianapolis, IN | 4A | 7.5°F | 5,250 |
| Wichita, KS | 4A | 12.4°F | 4,414 |
| Louisville, KY | 4A | 15.7°F | 3,936 |
| New Orleans, LA | 2A | 36.6°F | 1,176 |
| Boston, MA | 5A | 12.8°F | 5,545 |
| Baltimore, MD | 4A | 17.5°F | 4,484 |
| Portland, ME | 6A | 5°F | 6,795 |
| Detroit, MI | 5A | 7.3°F | 6,067 |
| Grand Rapids, MI | 5A | 6.8°F | 6,408 |
| Duluth, MN | 7 | -12.1°F | 9,115 |
| Minneapolis, MN | 6A | -6°F | 7,399 |
| Kansas City, MO | 4A | 7.2°F | 5,071 |
| St. Louis, MO | 4A | 12.2°F | 4,433 |
| Jackson, MS | 3A | 26.8°F | 2,222 |
| Billings, MT | 6B | -2.7°F | 6,754 |
| Charlotte, NC | 3A | 24.8°F | 3,058 |
| Raleigh, NC | 3A | 23.6°F | 3,153 |
| Fargo, ND | 6A | -13.9°F | 8,806 |
| Omaha, NE | 5A | 1.6°F | 5,833 |
| Manchester, NH | 5A | 7°F | 6,172 |
| Newark, NJ | 4A | 16.2°F | 4,701 |
| Albuquerque, NM | 4B | 22.4°F | 3,996 |
| Las Vegas, NV | 3B | 35.4°F | 1,836 |
| Reno, NV | 5B | 19.5°F | 4,669 |
| Albany, NY | 5A | 4.3°F | 6,357 |
| Buffalo, NY | 5A | 6.8°F | 6,466 |
| New York City, NY | 4A | 17.3°F | 4,553 |
| Cleveland, OH | 5A | 9°F | 5,516 |
| Columbus, OH | 4A | 9.8°F | 5,233 |
| Oklahoma City, OK | 3A | 19°F | 3,615 |
| Portland, OR | 4C | 29.4°F | 4,104 |
| Philadelphia, PA | 4A | 17.8°F | 4,510 |
| Pittsburgh, PA | 5A | 9.2°F | 5,572 |
| Providence, RI | 5A | 12.8°F | 5,478 |
| Columbia, SC | 3A | 27°F | 2,473 |
| Sioux Falls, SD | 6A | -6.3°F | 7,249 |
| Nashville, TN | 3A | 19.5°F | 3,364 |
| Amarillo, TX | 4B | 16°F | 3,872 |
| Dallas, TX | 2A | 27.4°F | 2,220 |
| Houston, TX | 2A | 34.3°F | 1,266 |
| San Antonio, TX | 2A | 33.1°F | 1,438 |
| Salt Lake City, UT | 5B | 15.6°F | 5,154 |
| Richmond, VA | 4A | 21.2°F | 3,736 |
| Burlington, VT | 6A | -1.7°F | 6,960 |
| Seattle, WA | 4C | 30°F | 4,376 |
| Spokane, WA | 5B | 11.8°F | 6,463 |
| Milwaukee, WI | 5A | 2.8°F | 6,450 |
| Charleston, WV | 4A | 14.8°F | 4,353 |
| Cheyenne, WY | 5B | 3.1°F | 6,959 |
Related tools
- BTU Calculator for sizing a single room's heating and cooling, a window AC or a space heater
- R-Value Calculator to total the insulation in a wall or attic before you pay to heat through it
- R-Value Chart for the insulation levels recommended in your climate zone
- Browse all free tools by Jake
What else to sort out with a new furnace
- Best Smart Thermostats: a two-stage furnace needs a thermostat that can call for both stages, or it never uses its low fire.
- Best Smoke and CO Detectors: a new gas appliance and flue is the time to put a CO alarm on every sleeping floor.
- Best Air Filters for Home: the filter that suits your return grille and blower, so a well-sized furnace isn't starved for air.
Sources and methodology
- Efficiency Maine, Heat Load Estimator: design load from past heating fuel use, HDD65 with (65 - design temperature)
- GreenBuildingAdvisor, Replacing a Furnace or Boiler: multiply fuel input by equipment efficiency, Btu per degree-hour at a 65F balance point
- Massachusetts Clean Energy Center, heat load from natural gas bills (summer baseline subtraction, rough-estimate caveats)
- ENERGY STAR National HVAC Design Report, Rev. 14: furnace heating capacity 100 to 140% of the design heat loss
- U.S. DOE Building America, Strategy Guideline: HVAC Equipment Sizing (Manual S: furnace within 140% of the heating load; input derated by efficiency)
- U.S. EIA, British thermal units: therm, natural gas per cubic foot, propane, heating oil, kWh
- NOAA NCEI, U.S. Climate Normals 1991-2020, annual heating degree days (base 65F)
- ASHRAE Handbook of Fundamentals 2021 climatic design conditions, 99% heating dry-bulb (via ashrae-meteo.info)
- 2021 IECC Table R301.1, climate zones by county
- Goodman GR9S80 and GR9S96 gas furnace specification sheets (input and output by model)
- Goodman AMST air handler specification sheet: electric heat kit kW at 240 V and the 208 V correction factor
- Federal Register 88 FR 87502: 95% AFUE minimum for non-weatherized gas furnaces from December 18, 2028
- Lee, Pergantis and Kircher (2026), Data-driven estimation of design heating loads for HVAC equipment sizing, arXiv preprint (74 houses; existing equipment averaged 2.96 times the bill-method load)
- Cross-validation: the fuel-use engine reproduces GreenBuildingAdvisor's worked example (647 Btu/h per °F, about 29,100 Btu/h at a 45 degree difference). The output math matches DOE Building America's example (60,000 Btu/h at 92.5% gives 55,500) and Goodman's 80% spec sheet line for line.
Every figure on this page is pinned in fixtures.json and recomputed before each
deploy; if the math and the words disagree, the build fails. All 71 cities' design
temperatures and degree days were re-fetched from the sources and matched on November 4, 2026.
Reviewed yearly. About Jake · Last reviewed November 4, 2026.
Cite this page
Free to cite or link in coursework, handouts, and articles — no permission needed.
Morrison, J. (2026, November 4). Furnace Size Calculator: Free BTU Sizing by Sq Ft or Gas Bill. DIYRated. https://diyrated.com/furnace-size-calculator/
Morrison, Jake. "Furnace Size Calculator: Free BTU Sizing by Sq Ft or Gas Bill." DIYRated, 4 Nov. 2026, diyrated.com/furnace-size-calculator.
Morrison, Jake. "Furnace Size Calculator: Free BTU Sizing by Sq Ft or Gas Bill." DIYRated. Last modified November 4, 2026. https://diyrated.com/furnace-size-calculator/
<a href="https://diyrated.com/furnace-size-calculator/">Furnace Size Calculator: Free BTU Sizing by Sq Ft or Gas Bill</a> by Jake Morrison, Licensed General Contractor — DIYRated
Embed this tool on your site
Free for HVAC contractors, energy auditors, weatherization programs, home inspectors and home-improvement bloggers. Required attribution is in the snippet. No fee, no account, no tracking attached to the embed.
<iframe
src="https://diyrated.com/furnace-size-calculator/embed/"
width="100%"
height="980"
loading="lazy"
style="border:1px solid #e5dcd0; border-radius:16px; max-width:900px;"
title="Furnace Size Calculator: heating load and furnace BTU size (DIYRated)">
</iframe>
<p style="font-size:12px;color:#666;margin-top:8px">
Furnace size calculator by
<a href="https://diyrated.com/furnace-size-calculator/">DIYRated</a>
· Reviewed by Jake Morrison, Licensed GC
</p>